Wire Size Calculator (Voltage Drop Method)

Minimum cable cross-section from the allowed voltage drop, with the next standard size in mm² and the AWG equivalent.

Your details

Unit system
Supply

230 V in Europe and Morocco, 120 V in North America.

V
Load given as

The design current of the circuit, or the rating of its breaker for a conservative result.

A

1 for heaters and resistive loads, about 0.8–0.9 for motors.

Distance from the panel or battery to the load. The return conductor is already counted.

Conductor

Hot conductor (IEC 60364-5-52, 1.25 × the 20 °C value) is the safe choice for design. The 20 °C value suits short, lightly loaded DC runs.

NF C 15-100 / IEC 60364-5-52 (supply from the public network): 3% for lighting, 5% for other uses. About 3% is usual for DC and solar wiring.

%

Results update as you type

Minimum cross-section

2.07 mm²

Standard section to use
2.5 mm²
AWG equivalent (≥ minimum)
14 AWG (2.08 mm²)
Load current
16 A
Voltage drop with the standard section
5.71 V
Voltage drop (%)
2.48%
Power lost in the cable
91.3 W
Resistivity used
0.0225 Ω·mm²/m

Voltage drop is only one criterion. The cable must also carry the current without overheating (IEC 60364-5-52 current-carrying tables, installation method, grouping, ambient temperature) and match its protective device. In French homes: 1.5 mm² up to 16 A, 2.5 mm² up to 20 A, 6 mm² for a 32 A cooking circuit.

This tool gives an estimate. It does not replace a qualified electrician or the rules that apply in your country.

Step-by-step solution
  1. L = 65 ft = 19.81 m ; b = 2 ; ρ = 0.0225 Ω·mm²/m
  2. ΔU max = 3 % × 230 V = 6.9 V
  3. S = b ρ L I ÷ ΔU = 2 × 0.0225 × 19.81 × 16 ÷ 6.9 = 2.067 mm²
  4. 2.5 mm² → ΔU = 5.71 V (2.48 %)

A cable that is too thin wastes energy as heat and, over a long run, delivers a voltage too low for the equipment at the end: lights dim, motors struggle to start and a 12 V fridge in a camper van cuts out. This wire size calculator finds the smallest conductor cross-section that keeps the voltage drop within the limit you choose.

It covers DC circuits (batteries, solar panels, vehicles, boats), single-phase AC and three-phase AC. Enter the voltage, the current or the power of the load, the one-way length of the cable and the allowed drop. The calculator returns the minimum section, the next standard size in mm² (1.5, 2.5, 4, 6, 10, 16, 25 mm² and so on), the equivalent AWG gauge used in North America, the actual drop with that standard size and the power lost in the cable.

The method is the one given in IEC 60364-5-52 and used by the French NF C 15-100 standard. It sizes a cable for voltage drop only: the result must also be checked against the cable’s current-carrying capacity and its protective device, which is why the calculator reminds you of the usual household pairs (1.5 mm² with 16 A, 2.5 mm² with 20 A, 6 mm² with 32 A). It is a design aid, not a substitute for a qualified electrician.

How to use this calculator

  1. Choose the supply: DC, single-phase or three-phase, and check the voltage (for three-phase, the voltage between phases, 400 V in Europe).
  2. Enter the load as a current in amps or as a power in watts. For AC, enter the power factor (1 for heaters).
  3. Enter the one-way length of the cable, from the panel or battery to the load.
  4. Choose copper or aluminium and the resistivity basis (hot conductor is the safe default).
  5. Set the allowed voltage drop: 3% for lighting, 5% for other circuits, about 3% for DC.
  6. Read the minimum section, the standard size to buy, the AWG equivalent and the real drop.

The formula

IEC 60364-5-52 (Annex G) gives the voltage drop in a cable as

u=b(ρLScos⁡φ+λLsin⁡φ)Iu = b \left( \rho \frac{L}{S} \cos\varphi + \lambda L \sin\varphi \right) I

where b=2b = 2 for DC and single-phase circuits (the current goes out and comes back) and b=1b = 1 for balanced three-phase circuits, ρ\rho the resistivity in Ω·mm²/m, LL the one-way length in m, SS the section in mm², λ=0.08\lambda = 0.08 mΩ/m the cable reactance and II the current. The relative drop is Δu=100 u/U0\Delta u = 100\,u/U_0, with U0U_0 the voltage between phase and neutral (U/3U/\sqrt{3} in three-phase).

Solving for the section, with the allowed drop ΔU=Δu⋅U0/100\Delta U = \Delta u \cdot U_0 / 100:

S=b ρ L Icos⁡φΔU−b λ L Isin⁡φS = \frac{b \, \rho \, L \, I \cos\varphi}{\Delta U - b \, \lambda \, L \, I \sin\varphi}

For DC or resistive loads (cos⁡φ=1\cos\varphi = 1) this reduces to S=b ρ L I/ΔUS = b\,\rho\,L\,I / \Delta U. The resistivity of a conductor in service is taken as 1.25 times its 20 °C value: 0.0225 Ω·mm²/m for copper and 0.036 for aluminium.

Worked example

Socket circuit. A 230 V single-phase circuit, 16 A, 20 m of copper cable, 3% allowed (6.9 V):

S=2×0.0225×20×166.9=2.09 mm2S = \frac{2 \times 0.0225 \times 20 \times 16}{6.9} = 2.09 \text{ mm}^2

The next standard size is 2.5 mm², which gives a real drop of 5.76 V (2.5%) and wastes about 92.2 W at full load. The AWG equivalent of the minimum is 13 AWG.

12 V solar or camper circuit. 10 A over 5 m with 3% (0.36 V): S=2×0.0225×5×10/0.36=S = 2 \times 0.0225 \times 5 \times 10 / 0.36 = 6.25 mm², so 10 mm² (drop 0.22 V, 1.88%). With the 20 °C resistivity the minimum falls to 4.79 mm² and 6 mm² would do; low voltages need surprisingly thick cables.

Three-phase motor. 400 V, 32 A, cos φ = 0.85, 50 m, 5%: the minimum is 2.67 mm², so 4 mm², with a real drop of 3.34%.

Common household circuits in France (NF C 15-100)

In French homes, the NF C 15-100 standard fixes the copper section and the maximum breaker rating for each kind of circuit. Typical pairs:

Circuit Copper section Breaker (max)
Lighting (up to 8 points) 1.5 mm² 16 A
Sockets (up to 8 outlets) 1.5 mm² 16 A
Sockets (up to 12 outlets) 2.5 mm² 20 A
Kitchen worktop sockets (up to 6) 2.5 mm² 20 A
Dedicated circuit: oven, washing machine, dishwasher 2.5 mm² 20 A
Cooking hob or cooker, single-phase 6 mm² 32 A

These sizes assume the usual lengths inside a dwelling. For a long run, to an outbuilding or a garden, check the voltage drop with the calculator and step up the section if needed: the section must satisfy both the current rating and the drop.

Cable section for direct current (DC)

At low voltage the same power needs a much larger current, and the allowed drop in volts is tiny: 3% of 12 V is only 0.36 V, against 6.9 V at 230 V. That is why DC wiring in vans, boats and off-grid solar systems often uses 6, 10 or 16 mm² cables for loads that a 1.5 mm² cable would feed easily at 230 V. Moving from 12 V to 24 V halves the current and cuts the required section by four for the same power and length.

For photovoltaic strings, the cable between panels and inverter is often sized for a drop of 1–3% to limit energy losses over the year, and solar cables (H1Z2Z2-K) are commonly 4 or 6 mm². Keep both conductors of a DC circuit the same size and count only the one-way length: the factor 2 in the formula already includes the return path.

Millimetres squared and AWG

Europe and most of the world size conductors by cross-section in mm² (IEC 60228). North America uses the American Wire Gauge, where a smaller number means a thicker wire: each step of 3 gauges roughly doubles the area. Some useful equivalents: 14 AWG ≈ 2.08 mm², 12 AWG ≈ 3.31 mm², 10 AWG ≈ 5.26 mm², 8 AWG ≈ 8.37 mm², 6 AWG ≈ 13.3 mm². The calculator picks the smallest AWG gauge whose area is at least the minimum section; because the two series do not line up, 2.5 mm² sits between 14 and 12 AWG.

Frequently asked questions

What voltage drop is allowed?

For installations supplied from the public low-voltage network, IEC 60364-5-52 and NF C 15-100 recommend at most 3% for lighting and 5% for other uses, measured from the origin of the installation. For DC and solar circuits about 3% is a common target, often less for long-term efficiency.

Should I enter the one-way or the round-trip length?

Enter the one-way length, from the panel or battery to the device. The factor b = 2 in the formula already accounts for the current returning through the second conductor in DC and single-phase circuits.

Why is my DC cable so thick?

At 12 V the current is about 19 times higher than at 230 V for the same power, and the allowed drop is only a few tenths of a volt. Both effects increase the section. Shorter runs or a higher system voltage (24 or 48 V) are the most effective cures.

Is the voltage drop the only thing to check?

No. The cable must also carry its current without overheating, depending on how it is installed, how many cables are grouped and the ambient temperature, and it must be protected by a matching breaker or fuse. Take the larger section of the two checks.

Can I use aluminium instead of copper?

Aluminium conducts about 60% as well as copper, so it needs roughly 1.6 times the section for the same drop. It is common for large supply cables but rarely used for small final circuits in homes, where terminals are designed for copper.

Does this replace an electrician?

No. The calculator applies the standard voltage-drop formula to give an estimate. Wiring work must follow the rules in force (NF C 15-100 in France) and is best designed and checked by a qualified electrician.