Choosing a circuit breaker starts with one number: the current the load draws. From there, two rules decide the rating. First, the breaker must not trip under normal use, so it has to be at least as large as the load current, and under the US National Electrical Code it must be 125 % of any continuous load, one that runs for three hours or more. Second, breakers only come in standard ratings, so you round up to the next one.
This breaker size calculator does both steps. Enter the load in watts with the voltage and power factor, or directly in amps, choose single-phase or three-phase, and pick the rule set: NEC for the United States and Canada-style installations, or IEC for the miniature circuit breakers (MCBs) used in Europe, Africa, the Middle East and most of Asia. The result is the load current, the minimum device rating after the continuous-load factor, the standard breaker to use and how much of its rating the load uses.
A breaker protects the wire, not the appliance. Whatever rating you pick, the conductor must be able to carry at least that current, so always continue with the wire size calculator, and check the voltage drop on long runs. For motors, use the motor full-load current from the three-phase motor amperage calculator and follow the specific motor rules, which allow larger breakers to ride through the starting current.
How to use this calculator
- Choose NEC or IEC and single-phase or three-phase.
- Give the load in watts (with the voltage and power factor) or in amps.
- Under NEC, tick continuous load if it can run for three hours or more.
- Read the breaker rating, the load current and, under NEC, the minimum rating after the 125 % factor.
- Check that your cable’s ampacity is at least the breaker rating before you install it.
The formula
Load current from power:
NEC 210.20(A) and 215.3: the overcurrent device must be rated at least the non-continuous load plus 125 % of the continuous load:
The breaker is the smallest standard rating from NEC 240.6(A) or from the IEC 60898-1 series. Under IEC 60364-4-43 the coordination rule is : design current, breaker rating, cable capacity.
Worked example
Water heater, NEC. A 4,800 W, 240 V tank water heater draws = 20 A. Storage water heaters are treated as continuous loads, so the device must be at least 20 × 1.25 = 25 A: a 25 A double-pole breaker.
Three-phase load, NEC. 50 kW at 480 V, cos φ = 0.85, running all day: = 70.75 A, × 1.25 = 88.44 A, so a 90 A breaker.
Heat pump, IEC. 11 kW on 400 V three-phase, cos φ = 0.9: = 17.64 A, so a 20 A MCB, with a cable rated for at least 20 A after derating.
Standard breaker sizes
| Standard | Ratings (A) |
|---|---|
| NEC 240.6(A) | 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 |
| IEC 60898-1 MCBs | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 |
Under the NEC, when the conductor ampacity does not match a standard rating, 240.4(B) allows the next size up for devices of 800 A or less, provided the conductor is not part of a multi-outlet branch circuit for cord-and-plug loads.
Continuous loads and the 125 % rule
A breaker in a warm panel carrying its full rating for hours runs hot, and standard breakers are tested to carry only 80 % of their rating continuously. That is the origin of the 125 % factor (1 / 0.8 = 1.25). Examples of continuous loads are electric water heaters, EV charging equipment, fixed space heating, and lighting in commercial buildings. A breaker listed for 100 % continuous operation removes the factor, but such devices are mainly found in large frames. IEC rules have no general 125 % factor; instead the designer checks the breaker against the design current and applies derating when many MCBs sit side by side.
Frequently asked questions
What size breaker do I need for 30 amps?
For a non-continuous load of 30 A, a 30 A breaker. If the 30 A runs for three hours or more under the NEC, the device must be at least 37.5 A, so a 40 A breaker with a conductor rated for 40 A.
What breaker for a 5,000 W load at 240 V?
5000 / 240 = 20.8 A. As a non-continuous load that is a 25 A breaker; as a continuous load 20.8 × 1.25 = 26 A, so a 30 A breaker on 10 AWG copper.
Can I use a bigger breaker to stop it tripping?
No. The breaker must protect the cable. A larger breaker on the same wire lets the wire overheat before anything trips. Find out why it trips (overload, fault, motor start) and resize the circuit, wire included, if needed.
What is the difference between NEC and IEC breaker sizing?
Both round up to a standard rating above the load current. NEC adds 125 % for continuous loads and uses its own rating list (15, 20, 25, 30 A…). IEC MCBs follow 6, 10, 16, 20, 25, 32 A… and the cable must satisfy Ib ≤ In ≤ Iz.
Does a motor follow the same rule?
No. Motor branch circuits use NEC Article 430: the breaker may be sized up to 250 % of the full-load current for inverse-time breakers so the motor can start, while overload relays provide the running protection.
Sources
- NFPA 70, National Electrical Code 2023 — 210.20(A), 215.3, 240.4, 240.6(A)
- IEC 60898-1:2015 — Circuit-breakers for overcurrent protection for household and similar installations
Last updated: