Heat Loss Calculator: Walls, Windows, Roof, Floor and Ventilation

Heat loss of a house through walls, windows, roof, floor and ventilation, in W, kW and kWh per year.

Your details

Unit system

The coldest temperature the heating must handle in your area (often −5 to −15 °C in Europe).

Building elements (area in m²)

Wall area net of windows. Factor b: 1 for outside air, about 0.5 for a floor on ground or an unheated space.

About 0.5 /h for a typical home with ventilation; up to 1 /h or more for a draughty old house.

vol/h
K·days

Results update as you type

Total heat loss

3.01 kW

Through the envelope
2,107 W
Through ventilation
899 W
Heat loss coefficient H
112.7 W/K
Total in BTU/h
10,254 BTU/h

Add 10 to 20 % for thermal bridges if the U-values do not include them, and size the heater with a small margin. A full EN 12831 study is room by room.

Step-by-step solution
  1. Walls: 0.3 × 100 = 30 W/K
  2. Windows: 1.4 × 15 = 21 W/K
  3. Roof: 0.2 × 80 = 16 W/K
  4. Ground floor: 0.5 × 0.3 × 80 = 12 W/K
  5. H_V = 0.34 × 0.5 × 198.2 m³ = 33.7 W/K
  6. ΔT = 48 °F → (79 + 33.7) × 26.67 = 3,005 W

Every hour in winter, a house loses heat in two ways: through its envelope (walls, windows, roof and floor conduct heat to the outside) and with the air that leaks out or is extracted by ventilation and replaced by cold outdoor air. The heating system must supply at least that much power on the coldest design day, and the sum over a whole winter is your heating bill.

This heat loss calculator follows the principles of the European standard EN 12831: for each element you enter its area and U-value (W/m²K), and the tool multiplies by the temperature difference between inside and outside. Ventilation losses use the volumetric heat capacity of air, 0.34 Wh/m³K, times the air change rate and the heated volume. Add degree-days for your location to turn the power into an estimate of the annual energy in kWh and its cost.

It is a whole-house estimate for comparing insulation options or sanity-checking a heat pump or boiler size. Professional sizing is done room by room with thermal bridges, intermittent heating and local design temperatures, so ask a heating engineer before you buy equipment.

How to use this calculator

  1. Enter the indoor temperature (19–21 °C) and the outdoor design temperature for your region.
  2. List each element: its area in m² (walls net of windows and doors), its U-value and the factor b (1 for outside air, about 0.5 for a floor on the ground or a wall next to an unheated garage).
  3. Enter the heated volume and the air change rate per hour.
  4. Optionally enter the heating degree-days of your location and a price per kWh.
  5. Read the total heat loss in kW, the split between envelope and ventilation, the coefficient H, the BTU/h figure and the yearly energy.

The formula

Transmission and ventilation heat loss coefficients (W/K):

HT=∑ibi Ui AiHV=0.34×n×VH_T = \sum_i b_i\,U_i\,A_i \qquad H_V = 0.34 \times n \times V

Design heat loss at the temperature difference ΔT=θint−θext\Delta T = \theta_{int} - \theta_{ext}:

Φ=(HT+HV)×ΔT[W]\Phi = (H_T + H_V) \times \Delta T \quad [\text{W}]

Annual heating need from degree-days DDDD (K·days):

Q=(HT+HV)×DD×241000[kWh]Q = \frac{(H_T + H_V) \times DD \times 24}{1000} \quad [\text{kWh}]

UU is in W/m²K, AA in m², nn in air changes per hour and VV in m³. 1 W equals 3.412 BTU/h.

Worked example

A detached house: 100 m² of walls at U = 0.30, 15 m² of windows at 1.4, an 80 m² roof at 0.20 and an 80 m² ground floor at 0.30 with b = 0.5. Heated volume 200 m³, 0.5 air change per hour, 19 °C inside and −7 °C outside (ΔT = 26 K).

  • HT=30+21+16+12=79H_T = 30 + 21 + 16 + 12 = 79 W/K, so 2,054 W through the envelope
  • HV=0.34×0.5×200=34H_V = 0.34 \times 0.5 \times 200 = 34 W/K, so 884 W through ventilation
  • Total: 2,938 W, about 2.94 kW

With 2,500 degree-days the yearly need is about 6,780 kWh, or 1,695 per year at 0.25 per kWh.

Indicative U-values for renovation

French energy-saving certificates (CEE) set minimum insulation levels that give useful targets: thermal resistance R ≥ 7 m²K/W for loft insulation (BAR-EN-101), R ≥ 3.7 for walls (BAR-EN-102), R ≥ 3 for floors (BAR-EN-103) and windows with Uw ≤ 1.3 W/m²K (BAR-EN-104). Since U is at most 1/R, an insulated loft has U below about 0.14 and an insulated wall below about 0.27. Uninsulated walls, single glazing and old roofs are many times worse, which is why they dominate the losses of older homes. Use the insulation calculator to get R and U from layer thicknesses.

Where the heat goes

In the example, ventilation is almost a third of the total: once the envelope is well insulated, air leakage becomes the next target (airtightness, heat-recovery ventilation). Windows lose more per m² than anything else, so their share grows quickly with glazed area.

Frequently asked questions

How do I calculate the heat loss of a house?

Multiply each element’s U-value by its area, add 0.34 × air changes × volume for ventilation, and multiply the sum by the indoor–outdoor temperature difference. The result is in watts.

What size heater do I need?

At least the design heat loss at your local outdoor design temperature, plus 10 to 20 % for thermal bridges and recovery after setbacks. Heat pumps are often sized close to the loss to avoid short cycling.

What are degree-days?

The sum over the heating season of how many degrees the daily mean temperature falls below a base temperature. Multiplying the heat loss coefficient by degree-days and 24 hours gives the yearly heating energy.

What air change rate should I use?

About 0.5 per hour for a typical home with controlled ventilation, 0.3 or less for an airtight house with heat-recovery ventilation, and 1 or more for an old draughty house.

How do I convert watts to BTU/h?

Multiply by 3.412. A 3 kW heat loss equals about 10,240 BTU/h.