Before you choose a cable, a contactor, a circuit breaker or a motor-protection relay, you need to know how many amps the motor will draw at full load. The power on the nameplate is not enough on its own: it is the mechanical output at the shaft, and the supply has to deliver more than that because of the motor’s losses (its efficiency η) and the reactive current that magnetises it (its power factor cos φ).
This calculator turns a rated power in kW or horsepower into the line current for a three-phase motor on 400 V, 480 V or any other voltage, or for a single-phase motor on 230 V or 120 V. It also gives the electrical input power, the apparent power in kVA that a generator or transformer must supply, and an estimate of the starting current with direct-on-line and star-delta starting. Choose Solve for → Motor power to find the largest motor a given current allows.
How to use this calculator
- Choose three-phase or single-phase supply.
- Enter the motor power in kW or hp and say whether it is the rated output (nameplate) or the electrical input.
- Enter the voltage: line-to-line for three-phase (400 V in Europe, 480 V in the US), line-to-neutral for single-phase.
- Enter the power factor and efficiency from the nameplate; the defaults (0.85 and 90 %) suit a mid-size four-pole motor.
- Optionally set the starting current ratio (6–8 is typical) to estimate the inrush.
The formula
For a balanced three-phase motor with rated shaft power , line-to-line voltage , power factor and efficiency :
For a single-phase motor the disappears: . If you enter the electrical input power, is left out. Other results:
One horsepower is 745.7 W (NIST SP 811). Direct-on-line starting draws ; star-delta starting cuts this to one third.
Worked example
A 7.5 kW three-phase motor on 400 V, cos φ 0.85, efficiency 90 %:
It draws 8.33 kW from the supply (9.80 kVA). With a starting ratio of 7, the direct-on-line inrush is about 99 A, or about 33 A with star-delta.
For comparison, a 2.2 kW single-phase motor on 230 V (cos φ 0.8, η 85 %) draws 14.07 A, and a 10 hp motor on 480 V (cos φ 0.86, η 90 %) draws 11.59 A.
Typical power factor and efficiency
Indicative full-load values for four-pole, 50 Hz induction motors (always prefer the nameplate):
| Rated power | cos φ | Efficiency (IE3) |
|---|---|---|
| 0.75–1.5 kW | 0.75–0.80 | 82–86 % |
| 4–7.5 kW | 0.82–0.85 | 88–91 % |
| 15–30 kW | 0.84–0.87 | 92–94 % |
| 55–110 kW | 0.86–0.90 | 94–95.5 % |
At part load both cos φ and efficiency drop, so a lightly loaded motor draws more current than its output alone would suggest. In the EU, Regulation (EU) 2019/1781 requires at least the IE3 efficiency class (IEC 60034-30-1) for most motors from 0.75 to 1,000 kW.
Starting current and protection
At standstill an induction motor behaves almost like a short circuit, so direct-on-line starting draws about six to eight times the rated current for a second or two. Star-delta starters connect the windings in star at first, which reduces both the starting current and the starting torque to one third. Soft starters and variable-frequency drives limit the inrush further. Breakers for motor circuits therefore use a trip curve that tolerates this surge while still protecting against overload. In the US, cable and protection sizing normally uses the tabulated full-load currents of NEC Table 430.250 rather than a calculated value; those table values are a little higher than the formula gives. See the wire size calculator for the cable.
Frequently asked questions
How many amps does a 7.5 kW motor draw at 400 V?
About 14 to 15 A per phase at full load. With cos φ 0.85 and 90 % efficiency the formula gives 14.15 A; check the nameplate, which states the exact rated current.
Why divide by √3 for three-phase?
In a balanced three-phase system the total power is √3 × line voltage × line current × cos φ. Dividing by √3 (about 1.732) gives the current in each line.
Should I use the voltage between phases or between phase and neutral?
For a three-phase motor use the line-to-line voltage (400 V, 480 V). For a single-phase motor use the voltage across its terminals, usually 230 V or 120 V.
What is a typical starting current?
Direct-on-line starting usually draws 6 to 8 times the full-load current; some high-efficiency motors reach 8 to 10 times. Star-delta reduces it to about one third, soft starters to 2–4 times.
Does the motor draw its full-load current all the time?
No. The current depends on the mechanical load. A pump or fan running at half load draws noticeably less, though not half, because the magnetising current remains.
Sources
- IEC 60034-30-1:2014 — Efficiency classes of line-operated AC motors (IE code)
- Commission Regulation (EU) 2019/1781 — ecodesign requirements for electric motors
- NIST SP 811 — Guide for the Use of the SI (horsepower conversion)
- Engineering ToolBox — Asynchronous induction motors, electrical properties