Every metre of wire has a small resistance, and in long runs or at high currents it adds up: the voltage at the far end drops, the cable warms up and energy is wasted. This wire resistance calculator gives you that resistance precisely, from the conductor material, its length, its size (cross-section in mm², diameter or AWG gauge) and its temperature.
It works for the conductors you actually meet: annealed copper as used in building wire, conductor-grade aluminium, pure metals for lab work, tungsten and nichrome for heating elements — or any resistivity you enter yourself. Choose whether to count a single conductor or a complete two-wire circuit, where the current goes out on one wire and comes back on the other.
Add the current and you also get the voltage drop and the power lost in the cable; add the supply voltage and the drop is expressed as a percentage. If what you need is the opposite — the cross-section required to stay under a given drop — use the wire size calculator.
How to use this calculator
- Pick the conductor material (annealed copper by default), or choose Other and type a resistivity.
- Give the size: cross-section in mm², bare-wire diameter, or AWG gauge.
- Enter the length of the cable and choose One conductor or Two-wire circuit (which doubles the path).
- Enter the conductor temperature: 20 °C for the reference value, 70 °C for a fully loaded PVC cable.
- Optionally add the current and supply voltage to get the voltage drop, its percentage and the heat loss.
The formula
The resistance of a uniform conductor is
with the resistivity at 20 °C (Ω·m), the length (m) and the cross-section (m²; 1 mm² = 10⁻⁶ m²). Annealed copper has Ω·mm²/m by definition (IACS).
Resistance rises with temperature, almost linearly over the usual range:
with /°C for copper and /°C for aluminium. AWG diameters follow mm. For a circuit carrying a current : and .
Worked example
A 25 m run of 2.5 mm² copper cable feeds a 16 A load on 230 V.
- One conductor at 20 °C: Ω
- Two-wire circuit (50 m of conductor): Ω
- Voltage drop: V, i.e. 2.4 % of 230 V
- Heat lost in the cable: W
At full load the conductor may reach 70 °C; the loop resistance then rises to 0.4126 Ω, about 20 % more.
Resistance per kilometre of common cable sizes
| Section (mm²) | Copper (Ω/km) | Aluminium (Ω/km) |
|---|---|---|
| 0.75 | 22.989 | 37.685 |
| 1 | 17.241 | 28.264 |
| 1.5 | 11.494 | 18.843 |
| 2.5 | 6.897 | 11.306 |
| 4 | 4.310 | 7.066 |
| 6 | 2.874 | 4.711 |
| 10 | 1.724 | 2.826 |
| 16 | 1.078 | 1.767 |
| 25 | 0.690 | 1.131 |
| 35 | 0.493 | 0.808 |
| 50 | 0.345 | 0.565 |
Values at 20 °C for a single conductor, from the nominal section. Real stranded cables (IEC 60228 class 2 and 5) have maximum resistances a few per cent higher because of stranding and tolerances.
AWG wire resistance chart (copper, 20 °C)
| AWG | Area (mm²) | Ω/km | Ω/1000 ft |
|---|---|---|---|
| 22 | 0.326 | 52.963 | 16.1432 |
| 20 | 0.518 | 33.309 | 10.1526 |
| 18 | 0.823 | 20.948 | 6.3850 |
| 16 | 1.309 | 13.174 | 4.0156 |
| 14 | 2.081 | 8.286 | 2.5254 |
| 12 | 3.309 | 5.211 | 1.5883 |
| 10 | 5.261 | 3.277 | 0.9989 |
| 8 | 8.366 | 2.061 | 0.6282 |
| 6 | 13.302 | 1.296 | 0.3951 |
| 4 | 21.151 | 0.815 | 0.2485 |
| 2 | 33.631 | 0.513 | 0.1563 |
| 1/0 | 53.475 | 0.322 | 0.0983 |
Each step of three gauges roughly halves the area and doubles the resistance; ten gauges multiply it by about ten.
Frequently asked questions
What is the resistance of copper wire per metre?
For annealed copper at 20 °C, divide 0.01724 by the cross-section in mm²: 1 mm² gives 17.241 Ω/km (0.0172 Ω/m), 2.5 mm² about 6.9 Ω/km. A 10 AWG wire has 0.9989 Ω per 1000 ft.
Why should I double the length for a circuit?
The current flows to the load through one conductor and returns through the other, so it crosses twice the cable length. Voltage drop calculations for single-phase and DC circuits always use this loop length.
How much does temperature change cable resistance?
For copper and aluminium about 0.4 % per °C. A cable running at 70 °C has roughly 20 % more resistance than at 20 °C, and 27 % more at 90 °C, which is why design standards use hot-conductor values.
Is aluminium cable worse than copper?
Aluminium is about 64 % more resistive (1 mm² gives 28.264 Ω/km), so it needs a section roughly 1.6 times larger for the same resistance. It is lighter and cheaper, which is why it is used for overhead lines and large feeders.
Why do two copper values appear in tables (1.68 and 1.72 × 10⁻⁸ Ω·m)?
The lower value is for very pure copper; 1.7241 × 10⁻⁸ Ω·m is the International Annealed Copper Standard (100 % IACS), the reference used for commercial conductors and wire tables.
Sources
- NBS Handbook 100 — Copper Wire Tables (International Annealed Copper Standard, α = 0.00393)
- HyperPhysics (Georgia State University) — Resistivity and temperature coefficient table
- HyperPhysics — Resistance and resistivity (R = ρL/A)
- ASTM B258 — Standard nominal diameters and cross-sectional areas of AWG sizes