Evaporation Rate Calculator for Pools and Water Surfaces

Estimate how much water a pool or open water surface loses to evaporation per hour, day and week.

Your details

Unit system

Indoor pools are usually kept 1–2 °C warmer than the water to limit evaporation.

%

Indoor pool halls: 0.05–0.15 m/s. The formula was fitted for low indoor air speeds.

Results update as you type

Evaporation rate

3.63 kg/h

Water lost per day
23 US gal
Water lost per week
161 US gal
Level drop per day
0.11 in
Latent heat carried away
2.46 kW
Vapour pressure at the water surface
1.067 inHg
Vapour pressure of the air
0.606 inHg

This is an engineering estimate; measured evaporation from real pools commonly differs by 20–40%.

Step-by-step solution
  1. p_w = eₛ(27.2 °C) = 3.612 kPa; p_a = 55% × eₛ(27.8 °C) = 2.052 kPa
  2. Y = 2501 − 2.361 × 27.2 = 2,436.7 kJ/kg
  3. W = 32.52 × 1.56 × (0.089 + 0.0782 × 0.1) / 2,436.7 × 0.5 = 1.008 g/s = 3.63 kg/h

Every open water surface loses water to the air, and the evaporation rate decides how often a pool needs topping up, how much a pool hall must be dehumidified and how much heat leaves with the vapour. Evaporating one kilogram of water takes about 2,440 kJ, so even a small residential pool can lose several kilowatts of heat continuously.

This calculator estimates evaporation with the Carrier equation as recommended by the ASHRAE Handbook for indoor pools (natatoriums). It needs the water surface area, the water temperature, the air temperature and relative humidity, the air speed across the surface, and the type of use, which sets the ASHRAE activity factor: splashing swimmers, waves and slides multiply the free surface and the evaporation. You get the rate in kg per hour, the water lost per day and per week, the drop in water level, and the latent heat carried away.

Evaporation is driven by the difference between the vapour pressure at the water surface (saturated air at the water temperature) and the vapour pressure of the room air. Warm water and dry air evaporate fast; warm, humid air above cooler water slows it almost to zero. The result is an engineering estimate — independent measurements show actual pools often differ by 20–40% — but it is the standard starting point for sizing dehumidifiers and planning water use.

How to use this calculator

  1. Enter the water surface area (length × width for a rectangular pool).
  2. Enter the water temperature and the air temperature above it.
  3. Enter the relative humidity of the air (hall or outdoor).
  4. Enter the air speed over the water: about 0.05–0.15 m/s in a typical pool hall.
  5. Choose the type of use; use “unoccupied” for a calm pond, tank or a pool at night.
  6. Read the evaporation rate, the daily and weekly loss and the level drop.

The formula

The Carrier equation in SI units, as given by ASHRAE:

W=A (pw−pa) (0.089+0.0782 V)Y×FaW = \frac{A\,(p_w - p_a)\,(0.089 + 0.0782\,V)}{Y} \times F_a
  • WW: evaporation, kg/s; AA: water surface, m²; VV: air speed, m/s
  • pwp_w: saturation vapour pressure at the water temperature, kPa
  • pap_a: vapour pressure of the air =RH100×es(Tair)= \frac{RH}{100} \times e_s(T_{air}), kPa
  • YY: latent heat of vaporisation at the water temperature, kJ/kg (≈2501−2.361 T\approx 2501 - 2.361\,T)
  • FaF_a: activity factor (0.5 unoccupied or residential, up to 1.5 for wave pools)

Saturation pressures use Buck’s formula es=0.61121exp⁡(17.502 T240.97+T)e_s = 0.61121 \exp\left(\frac{17.502\,T}{240.97 + T}\right) kPa. Multiplying WW by YY gives the latent heat load in kW.

Worked example

A residential indoor pool of 32 m² (8 m × 4 m), water at 27 °C, air at 28 °C and 55% humidity, air speed 0.1 m/s, activity factor 0.5.

  • pw=3.565p_w = 3.565 kPa and pa=0.55×es(28)=2.079p_a = 0.55 \times e_s(28) = 2.079 kPa, a difference of 1.486 kPa
  • Y=2501−2.361×27=2,437.3Y = 2501 - 2.361 \times 27 = 2{,}437.3 kJ/kg
  • W=32×1.486×0.09682/2,437.3×0.5W = 32 \times 1.486 \times 0.09682 / 2{,}437.3 \times 0.5 → 3.4 kg/h

That is about 82 litres per day (2.6 mm of water level) and 571 litres per week, with about 2.3 kW of heat leaving the water. A busy 25 m × 12.5 m public pool at 28 °C (air 29 °C, 55%) loses about 70.5 kg/h, roughly 11.8 m³ per week.

How to reduce evaporation

  • Cover the pool when it is not in use: covers cut evaporation from the covered surface almost entirely, and with it most of the heat loss.
  • Keep the air warmer than the water: ASHRAE recommends air 1–2 °C above water temperature in pool halls, which lowers the vapour pressure difference without making the hall feel muggy.
  • Do not over-dry the air: relative humidity of 50–60% is the usual design target; drier air speeds evaporation and raises energy use.
  • Keep air movement over the water gentle: supply air should sweep the walls and windows, not blow across the pool surface.
  • Avoid overheating the water: each extra degree raises the surface vapour pressure by about 6%.

Evaporation from other water surfaces

The same physics applies to ponds, tanks, fountains and reflecting pools: use the unoccupied factor (0.5) for a calm surface. Outdoors, sunshine and wind dominate, and daily evaporation in summer is often 3–8 mm in temperate climates and more in hot, dry regions. Meteorological services estimate such open-water evaporation with more complete methods (Penman equation, evaporation pans), so for outdoor pools and reservoirs treat this calculator’s result as an order of magnitude.

Frequently asked questions

How much water does a pool lose to evaporation?

Indoor residential pools typically lose about 2–4 mm of water level per day; busy public pools more. Outdoors, losses of 5 mm or more per summer day are common because of sun and wind.

What is the activity factor?

A multiplier from ASHRAE that adjusts the Carrier equation to the level of use: 0.5 for an unoccupied or residential pool, 0.65 for condominium and therapy pools, 0.8 for hotels, 1.0 for public pools and spas, and 1.5 or more for wave pools and slides.

Why does humid air reduce evaporation?

Evaporation is driven by the difference between the vapour pressure at the water surface and in the air. The more water vapour the air already contains, the smaller that difference and the slower the evaporation.

How accurate is the estimate?

The Carrier equation with activity factors is the long-standing ASHRAE method, but comparisons with measured data show average deviations of about 20–40%. It is adequate for planning and first sizing; measure actual water use for precise figures.

How much heat does evaporation remove?

About 2,440 kJ for every kilogram evaporated at pool temperatures, so 1 kg/h corresponds to roughly 0.68 kW of heat drawn from the water.