Reynolds Number Calculator

Re = ρvD/μ for water, air or any fluid, in pipes, rectangular ducts or along a plate, with the flow regime.

Your details

Unit system

Results update as you type

Reynolds number Re

77,126

Flow regime
Turbulent
Kinematic viscosity ν = μ/ρ
1.00381 mm²/s

Step-by-step solution
  1. Re = ρ v L / μ = 998.2 × 1.524 × 0.0508 / 1.002×10⁻³ = 77,125.6

The Reynolds number is the single most useful figure in fluid mechanics. It compares the inertia of a moving fluid, which tends to create eddies, with its viscosity, which smooths them out. When viscosity wins (low Re) the fluid slides along in orderly layers: the flow is laminar. When inertia wins (high Re) the motion becomes chaotic and mixes vigorously: the flow is turbulent. Which regime you are in decides how much pressure a pipe loses, how fast heat is transferred, how a dye spreads and which friction formula is valid.

This calculator works out Re for water at 20 °C, air at 20 °C or any fluid whose density and viscosity you know (dynamic μ or kinematic ν). Choose the geometry: a round pipe uses its inner diameter, a rectangular duct or any other section uses the hydraulic diameter Dh=4A/PD_h = 4A/P, and a flat plate uses the distance from the leading edge. The result comes with the flow regime and the arithmetic.

Because Re is dimensionless, two flows with the same Reynolds number behave alike even if one is a model in a water tunnel and the other a full-size ship, which is why engineers quote it everywhere from blood flow to aircraft wings.

How to use this calculator

  1. Choose the fluid: water or air at 20 °C, or Other to type its properties.
  2. For another fluid, give either the density and dynamic viscosity (mPa·s = cP) or the kinematic viscosity (mm²/s = cSt).
  3. Enter the mean velocity, the volume flow divided by the cross-section. The flow rate calculator converts L/min into m/s.
  4. Pick the geometry and enter the diameter, the duct sides, the area and wetted perimeter, or the distance along the plate.
  5. Read Re, the regime and, for ducts, the hydraulic diameter. Solve for finds the velocity or diameter that gives a chosen Re, for instance the largest velocity that keeps a pipe laminar.

The formula

The Reynolds number is the ratio of inertial to viscous forces:

Re=ρ v Lμ=v LνRe = \frac{\rho \, v \, L}{\mu} = \frac{v \, L}{\nu}

where ρ\rho is the density (kg/m³), vv the mean velocity (m/s), LL the characteristic length (m), μ\mu the dynamic viscosity (Pa·s) and ν=μ/ρ\nu = \mu/\rho the kinematic viscosity (m²/s). With consistent units Re has no unit at all.

For a round pipe LL is the inner diameter DD. For any other full-flowing section it is the hydraulic diameter:

Dh=4AP,rectangle a×b:  Dh=2aba+bD_h = \frac{4A}{P}, \qquad \text{rectangle } a \times b: \; D_h = \frac{2ab}{a+b}

For a circle, 4(πD2/4)/(πD)=D4 (\pi D^2/4) / (\pi D) = D, so both definitions agree. Usual limits in pipes: Re<2300Re < 2300 laminar, 23002300–40004000 transitional, Re>4000Re > 4000 turbulent.

Worked example

Water in a pipe. Water at 20 °C (ρ\rho = 998.2 kg/m³, μ\mu = 1.002 mPa·s, so ν\nu ≈ 1.004 mm²/s) flows at 1.5 m/s in a pipe of 50 mm inner diameter:

Re=998.2×1.5×0.050.001002≈74,716Re = \frac{998.2 \times 1.5 \times 0.05}{0.001002} \approx 74{,}716

Far above 4,000: the flow is turbulent, as it is in almost every domestic and industrial water pipe. To stay laminar in the same pipe the water would have to crawl below about 0.05 m/s; at 0.02 m/s, Re is only 996.

Air in a duct. Air at 20 °C (ν\nu ≈ 15.16 mm²/s) moves at 4 m/s in a 300 × 200 mm ventilation duct. The hydraulic diameter is 2×0.3×0.2/0.52 \times 0.3 \times 0.2 / 0.5 = 0.24 m, and Re ≈ 63,334, again turbulent.

Where the 2,300 and 4,000 limits come from

Osborne Reynolds injected a thin streak of dye into water flowing through glass tubes in 1883. At low speed the streak stayed a straight thread; above a certain speed it suddenly broke up and coloured the whole tube. He showed that the change depends only on the combination ρvD/μ\rho v D / \mu. In ordinary pipes with some vibration and inlet disturbance, laminar flow is reliable below about 2,300, fully turbulent flow sets in above about 4,000, and in between the flow flickers from one regime to the other. Very carefully smoothed experiments have kept water laminar beyond Re = 40,000, so the limits are practical rules, not laws of nature.

Situation Characteristic length Typical transition
Round pipe Inner diameter DD 2,300 – 4,000
Duct, channel, annulus Hydraulic diameter 4A/P4A/P About the same as pipes (turbulent)
Flat plate boundary layer Distance xx from the leading edge About 5×1055 \times 10^5
Sphere in a fluid Sphere diameter Drag crisis near 3×1053 \times 10^5

Why the regime matters

In laminar flow the friction factor is exactly 64/Re64/Re, pressure loss grows linearly with flow and fluids barely mix. In turbulent flow the loss grows roughly with the square of the velocity, wall roughness starts to count, and heat transfer is far more efficient. The pressure drop calculator uses your Reynolds number to pick the right friction law (Hagen–Poiseuille or Colebrook) and returns the pressure and head loss of a pipe run. Temperature changes the result a lot through viscosity: water at 60 °C is about half as viscous as at 20 °C, so Re doubles at the same speed.

Frequently asked questions

What is a good Reynolds number?

There is no good or bad value; it tells you the regime. In pipes, Re below about 2,300 means laminar flow, 2,300 to 4,000 is transitional, and above 4,000 the flow is turbulent. Most water mains, heating loops and ventilation ducts run turbulent.

Does the Reynolds number have units?

No. Density times velocity times length divided by dynamic viscosity cancels every unit, as long as you use a consistent set (SI: kg/m³, m/s, m, Pa·s). Mixing millimetres with metres or centipoise with Pa·s is the most common mistake, which this calculator handles for you.

What is the difference between dynamic and kinematic viscosity?

Dynamic viscosity μ (Pa·s or cP) measures internal friction. Kinematic viscosity ν (m²/s or cSt) is μ divided by density. Re = ρvL/μ = vL/ν, so either works. Oil datasheets often give ν in cSt at 40 °C.

How do I compute the Reynolds number of a rectangular or square duct?

Replace the diameter with the hydraulic diameter Dh = 4A/P, four times the flow area divided by the wetted perimeter. For a rectangle a × b this is 2ab/(a + b); for a square of side a it is simply a.

Why is the critical Reynolds number different for a flat plate?

Over a plate the length used is the distance from the leading edge, not a diameter, and the boundary layer grows along the surface. Transition there usually happens near Re_x ≈ 500,000, so the pipe limits do not apply.