Every cable has resistance, so part of the supply voltage is lost along the way before it reaches the load. Too much voltage drop makes lights dim, motors run hot and start poorly, and electronics misbehave; it also wastes energy as heat in the wire. This calculator works out that drop for an existing or planned cable.
Enter the supply voltage, the load current, the one-way length and the conductor size, either as an AWG/kcmil gauge or as a cross-section in mm², then choose copper or aluminum. The calculator gives the drop in volts, the percentage of the supply voltage, the voltage left at the load, the resistance of one conductor and the power lost in the cable. It handles DC and single-phase circuits (current flows out and back, so the length counts twice) and three-phase circuits (line-to-line drop with the √3 factor).
The result is compared with the NEC recommendation (3% on a branch circuit, 5% in total) and with the IEC 60364-5-52 limits used in Europe, Morocco and much of the world. To size a cable for a target drop instead, use the wire size calculator.
How to use this calculator
- Choose DC, single-phase or three-phase.
- Enter the supply voltage (line-to-line for three-phase) and the current drawn by the load.
- Enter the one-way cable length in metres or feet.
- Give the conductor size in mm² or pick an AWG/kcmil gauge, and choose copper or aluminum.
- Keep 75 °C for a loaded cable (as in NEC tables) or choose 20 °C for the cold value. For motors, enter the power factor.
- Read the drop in volts and percent, the voltage at the load, and the NEC and IEC checks.
The formula
The resistance of one conductor of length and cross-section is:
with and for copper, and for aluminum. Then:
With a power factor below 1, is replaced by , where is the IEC default cable reactance. At 75 °C copper’s resistivity is 2.0918 × 10⁻⁸ Ω·m.
Worked example
A 230 V single-phase circuit feeds 16 A through 30 m of 2.5 mm² copper at 75 °C:
- Ω per conductor
- V, i.e. 3.49%, leaving 221.97 V at the load
That is above 3%, so it is too much for a lighting circuit under IEC rules but fine for other uses. Cold (20 °C) the drop would be 6.6 V (2.87%).
US example: 120 V, 16 A, 100 ft of 12 AWG copper drops 6.17 V (5.14%), above the NEC’s 5% total. 10 AWG brings it to 3.23% and 8 AWG to 2.03%. A 400 V three-phase motor line, 32 A over 50 m of 6 mm², drops 9.66 V (2.42%).
NEC 3% and 5% recommendations
The US National Electrical Code does not make voltage drop a mandatory limit for ordinary circuits. Informational notes to 210.19(A) (branch circuits) and 215.2(A) (feeders) say that sizing conductors to keep the drop at or below 3% at the farthest outlet, with 5% in total for feeder plus branch circuit, provides reasonable efficiency of operation. Some articles do set binding limits (for example sensitive electronic equipment and fire pumps), and many engineers and local codes treat the 3%/5% figures as the design standard.
IEC 60364-5-52 limits (Europe, Morocco, NF C 15-100)
| Installation | Lighting | Other uses |
|---|---|---|
| Supplied from the public low-voltage network | 3% | 5% |
| Supplied from a private substation | 6% | 8% |
The limits apply between the origin of the installation and the equipment, and are set by Annex G of IEC 60364-5-52, adopted in France through NF C 15-100. Motor starting can tolerate larger temporary drops.
Frequently asked questions
What is an acceptable voltage drop?
In the US, the NEC recommends no more than 3% on a branch circuit and 5% for feeder plus branch together. Under IEC rules, 3% for lighting and 5% for other uses on a public supply.
Why is the length doubled for single-phase circuits?
Current flows out on one conductor and back on the other, so both add resistance. In a balanced three-phase circuit the return currents cancel and the line-to-line drop uses the factor √3 instead of 2.
How do I reduce voltage drop?
Use a larger conductor, shorten the run, raise the supply voltage (240 V instead of 120 V halves the current for the same power), or switch from aluminum to copper.
Is aluminum wire worse for voltage drop?
Aluminum’s resistivity is about 64% higher than copper’s, so an aluminum conductor needs roughly two AWG sizes larger, or about 1.6 times the cross-section in mm², for the same drop.
Does temperature affect voltage drop?
Yes. Copper’s resistance rises about 0.39% per °C: from 20 °C to 75 °C it increases by about 22%. NEC Chapter 9 Table 8 values are given at 75 °C, which is why it is the default here.
Sources
- NFPA 70 — National Electrical Code, 210.19(A) and 215.2(A) informational notes; Chapter 9 Table 8
- IEC 60364-5-52:2009 — Low-voltage installations, wiring systems (Annex G: voltage drop)
- NBS Handbook 100 — Copper Wire Tables (annealed copper standard, 1.7241 × 10⁻⁸ Ω·m at 20 °C)
- ASTM B258 — Standard nominal diameters and cross-sectional areas of AWG sizes
Last updated: