kVA Calculator: kVA to Amps, kW and Transformer Size

Convert kVA to amps, amps to kVA and kVA to kW for single- and three-phase supplies, and size a transformer.

Your details

Supply

Three-phase: the line-to-line voltage (400 V in Europe, 208 V or 480 V in North America). Single-phase: 230 V, 120 V or 240 V.

V
A

1 for heaters, about 0.8–0.9 for motors and mixed commercial loads.

Results update as you type

Apparent power S

69.282 kVA

Real power P
55.426 kW
Reactive power Q
41.569 kvar

Step-by-step solution
  1. S = √3 × V × I / 1000 = √3 × 400 × 100 / 1000 = 69.282 kVA
  2. P = S × cos φ = 69.282 × 0.8 = 55.426 kW

Generators, UPS units and transformers are rated in kVA (kilovolt-amperes), while the appliances they feed are listed in kW and the cables are chosen in amps. Moving between the three is a daily task for electricians, facility managers and anyone buying a generator, and the conversion depends on two things people often forget: whether the supply is single-phase or three-phase, and the power factor of the load.

This kVA calculator has four modes. kVA from amps gives the apparent power a circuit carries from its voltage and current. Amps from kVA works the other way, for example to find the full-load current of a 50 kVA generator. kW from kVA splits apparent power into real power (kW, what does useful work) and reactive power (kvar). Transformer size starts from your total load in kW, divides by the power factor, adds a spare-capacity margin and returns the next preferred kVA rating from the IEEE C57.12.00 series, together with the rated current on the secondary side.

For three-phase systems always enter the line-to-line voltage (400 V, 415 V, 480 V…). If you only know the phase-to-neutral value, multiply it by √3 first (230 V × √3 ≈ 400 V). To go from the current to a protective device and a cable, continue with the breaker size calculator and the wire size calculator.

How to use this calculator

  1. Choose what you want: kVA from amps, amps from kVA, kW from kVA or transformer size.
  2. Select single-phase or three-phase and enter the voltage (line-to-line for three-phase).
  3. Enter the current, the kVA or the load in kW, depending on the mode.
  4. Enter the power factor (cos φ). Resistive heating is 1; motors and mixed buildings are usually 0.8 to 0.9.
  5. For a transformer, add a spare capacity percentage and read the standard rating, the required kVA, the loading today and the secondary current.

The formula

Apparent power, real power and reactive power form the power triangle (IEEE Std 1459):

S=P2+Q2P=Scos⁡φQ=Ssin⁡φS = \sqrt{P^2 + Q^2} \qquad P = S \cos\varphi \qquad Q = S \sin\varphi

Single-phase, with voltage VV and current II:

S [kVA]=V×I1000I=1000 SVS\,[\text{kVA}] = \frac{V \times I}{1000} \qquad I = \frac{1000 \, S}{V}

Balanced three-phase, with the line-to-line voltage VLV_L and the line current ILI_L:

S [kVA]=3 VL IL1000IL=1000 S3 VLS\,[\text{kVA}] = \frac{\sqrt{3} \, V_L \, I_L}{1000} \qquad I_L = \frac{1000 \, S}{\sqrt{3} \, V_L}

Transformer sizing: Sreq=Pcos⁡φ×(1+m)S_\text{req} = \dfrac{P}{\cos\varphi} \times (1 + m) with the margin mm, rounded up to the next preferred rating.

Worked example

kVA from amps. A three-phase board at 400 V carries 100 A per line with cos φ = 0.8:

S=3×400×1001000=69.28 kVAS = \frac{\sqrt{3} \times 400 \times 100}{1000} = 69.28\ \text{kVA}

Real power PP = 55.43 kW, reactive power QQ = 41.57 kvar.

Amps from kVA. A 50 kVA single-phase generator at 240 V can deliver I=50,000/240I = 50{,}000 / 240 = 208.3 A.

Transformer size. A workshop needs 60 kW at cos φ = 0.8 on a 400 V three-phase supply, with 20 % spare: 60/0.8=7560 / 0.8 = 75 kVA, × 1.2 = 90 kVA, so the next three-phase rating is 112.5 kVA. Today it runs at 66.7 % of its rating, and its rated secondary current is 162.4 A.

Standard transformer ratings

Distribution transformers come in fixed preferred ratings. Three-phase units are roughly three times the single-phase steps, which is why sizes such as 45, 112.5 and 225 kVA exist. The calculator uses these series:

Supply Preferred kVA ratings
Single-phase 5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500, 833, 1250, 1667, 2500
Three-phase 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3750, 5000

Dry-type and IEC units follow similar steps (for example 100, 160, 250, 400, 630, 1000 kVA in Europe), so check the catalogue of your supplier before ordering.

Why kVA and not kW?

A transformer or generator heats up with the current that flows through its windings, whatever the phase angle. Two loads of 80 kW, one at cos φ = 1 and one at cos φ = 0.8, draw 80 kVA and 100 kVA respectively, and the second needs a bigger machine. That is why the rating is given in kVA, and why improving the power factor with capacitors frees capacity on an existing transformer.

Frequently asked questions

How do I convert kVA to amps?

Single-phase: amps = kVA × 1000 / volts. Three-phase: amps = kVA × 1000 / (√3 × line-to-line volts). A 100 kVA three-phase transformer at 400 V gives about 144 A per line.

How do I convert kVA to kW?

Multiply by the power factor: kW = kVA × cos φ. With the common generator rating of cos φ = 0.8, a 100 kVA set delivers 80 kW of real power.

What size transformer do I need?

Divide the expected simultaneous load in kW by the power factor to get kVA, add a margin for growth (often 20–25 %), then choose the next standard rating up. Motors with heavy starting currents may justify a further step.

Which voltage do I use for three-phase?

The line-to-line voltage, measured between two phases (400 V, 415 V, 480 V). If you use the phase-to-neutral voltage, the formula becomes S = 3 × V × I instead of √3 × V × I; both give the same result.

Is 1 kVA equal to 1 kW?

Only when the power factor is 1, as with heaters and incandescent lamps. For any inductive or electronic load, 1 kVA carries less than 1 kW of useful power.