The U-value (thermal transmittance) tells you how many watts of heat pass through one square metre of a wall, roof or floor for every degree of difference between inside and outside. The lower it is, the better the element insulates: an uninsulated concrete wall is around 3 W/(m²·K), a well-insulated modern wall 0.15–0.25.
This calculator builds the U-value layer by layer, exactly as the international method ISO 6946 does. List the layers from inside to outside — plaster, insulation, masonry, render, an air gap — with their thickness. Each material comes with a design conductivity λ from the French Th-bât rules; type your own λ from a product datasheet to override it. You get the U-value, the total thermal resistance, the share of each layer, the US equivalents and, with an area and two temperatures, the heat lost through the element. For a whole house, carry the U-values into the heat loss calculator.
How to use this calculator
- Choose the element: wall, roof / ceiling or floor. This sets the surface resistances.
- Enter the layers from inside to outside: pick a material and its thickness. Leave λ blank to use the default, or type the certified λ of your product.
- For an unventilated cavity choose air gap: its resistance comes from the ISO 6946 table, not from λ.
- Optionally enter the area and the indoor and outdoor temperatures to get the heat loss in watts.
- Read the U-value, the total R and the layer table; open the steps to check every term.
The formula
Each homogeneous layer of thickness (m) and conductivity (W/(m·K)) has a thermal resistance . Resistances in series add up, together with the two surface resistances:
| Heat flow | ||
|---|---|---|
| Horizontal (walls) | 0.13 | 0.04 |
| Upward (roofs, ceilings) | 0.10 | 0.04 |
| Downward (floors) | 0.17 | 0.04 |
An unventilated air layer of 25 mm or more adds about 0.18 m²·K/W in a wall. Heat loss through an area is then .
Worked example
A concrete wall lined inside with 120 mm of glass wool and plasterboard, rendered outside:
| Layer | R |
|---|---|
| Plasterboard 13 mm, λ 0.25 | 0.052 |
| Glass wool 120 mm, λ 0.035 | 3.429 |
| Concrete 200 mm, λ 2.0 | 0.100 |
| Render 15 mm, λ 1.3 | 0.012 |
m²·K/W, so U = 0.266 W/(m²·K). Without the insulation and plasterboard, the same wall would have U ≈ 3.55. For 20 m² of this wall with 19 °C inside and −7 °C outside (ΔT = 26 K), the loss is W.
Typical U-values and requirements
| Element | Typical U, W/(m²·K) |
|---|---|
| Solid concrete or stone wall, uninsulated | 2–3.5 |
| Wall with 100 mm of mineral wool | 0.3–0.35 |
| High-performance new wall | 0.12–0.2 |
| Loft with 300 mm of insulation | 0.12–0.15 |
In France, renovation grants (CEE and MaPrimeRénov’) require the added insulation alone to reach R ≥ 3.7 m²·K/W on walls, 6 under sloping roofs, 7 in lost attics and 3 on low floors (rules in force in 2026). The calculator shows the R of your insulation layers next to these thresholds. New buildings under RE2020 are judged on whole-building indicators rather than a fixed U per wall.
What ISO 6946 leaves out
The simple layer sum assumes uniform layers. Timber studs or metal fixings crossing the insulation (thermal bridges) raise the real U-value, sometimes by 10–20 %; ISO 6946 has an extended method for such inhomogeneous layers. Junctions between walls, floors and windows are handled separately with linear thermal bridges. Ground floors use ISO 13370. Use the insulation calculator to find the thickness needed for a target R.
Frequently asked questions
What is a good U-value for a wall?
Below about 0.3 W/(m²·K) is good for a renovated wall, and new low-energy buildings reach 0.15–0.2. An uninsulated masonry wall is typically 1.5 to 3.
What is the difference between U-value and R-value?
R is resistance to heat flow (m²·K/W): higher is better and layer resistances add up. U is the inverse of the total resistance including surfaces: lower is better.
Where do I find λ for my insulation?
On the label or declaration of performance of the product, as the declared λ (λD) in W/(m·K). In France, ACERMI certificates give the certified value. Enter it in the λ field of the layer.
How do I convert a U-value to US units?
Divide by 5.678: 0.28 W/(m²·K) is about 0.049 BTU/(h·ft²·°F). The whole-element US R-value is 5.678 times the SI resistance.
Does an air gap insulate?
A sealed air gap adds a modest resistance, about 0.18 m²·K/W in a wall once it is 25 mm or wider. A ventilated cavity adds almost nothing: layers outside it are then ignored.
Sources
- ISO 6946:2017 — Thermal resistance and thermal transmittance, calculation methods
- Règles Th-bât, fascicule Matériaux (2017) — design λ values
- Règles Th-bât, fascicule Parois opaques (2017) — surface and air-layer resistances
- CEE sheet BAR-EN-102, wall insulation (R ≥ 3.7), version from 1 Jan 2025
Last updated: